Configuring dnp3, Changing 32-bit register format, Dnp options – SATEC EM132-133 Manual User Manual

Page 96

background image

‎Chapter 5 Configuring T H E E M 1 3 X S E R I E S

96

EM13x Series SMART MULTIFUNCTION METER

Changing 32-bit Register Format

The EM13X Series allows you to read 32-bit Modbus analog registers,
energy counters and binary counters either in integer format, or in
IEEE single precision floating point format.

The 32-bit MODBUS registers are factory-set to integer format. To
change the register format:
Select Protocol Setup from the Meter Setup menu, and click on the
Modbus Registers tab.
Change the 32-bit register format in the MODBUS Options pane.
Click Send to download your setup to the meter.

Configuring DNP3

Refer to the EM13X Series DNP3 Reference guide for information on
the DNP3 protocol implementation and a list of the available data
points.

DNP Options

Select Protocol Setup from the Meter Setup menu and click on the
DNP Options tab.

Figure ‎5-21: Protocol Setup Dialog Box – DNP Options Tab

The following table describes available options. Refer to the DNP3 Data
Object Library document available from the DNP User’s Group on the
DNP3 object types.

Table 19: DNP Options

Parameter

Options

Default

Description

Binary Inputs (BI)

Binary Input Object

Single-bit

With Status

Single-bit

The default BI object variation for

requests with qualifier code 06 when no

specific variation is requested

Analog Inputs (AI)