‎Chapter 5 Configuring T H E E M 1 3 X S E R I E S

EM13x Series SMART MULTIFUNCTION METER

71

Figure ‎5-7: General Setup Dialog Box – Device Options Tab

Power Calculation Modes

The power calculation mode option allows you to change the method
for calculating reactive and apparent powers in presence of high
harmonics. The options work as follows:

When the reactive power calculation mode is selected, active and

reactive powers are measured directly and apparent power is

calculated as:

2

2

Q

P

S

This mode is recommended for electrical networks with low

harmonic distortion, commonly with THD < 5% for volts, and THD
< 10% for currents. In networks with high harmonics, the second

method is preferable.

When the non-active power calculation mode is selected, active

power is measured directly, apparent power is taken as product S
= V x I, where V and I are the RMS volts and amps, and reactive

power (called non-active power) is calculated as:

2

2

P

S

N

Configuring Digital Inputs

The EM13X Series can be provided with two digital inputs (standard)
and 4 or 12 optional digital inputs that can be linked to control
setpoints to give an indication on input status change (see

Configuring

Alarm/Control Setpoints

), or can be linked to general pulse counters to

count incoming pulses (see

Configuring Counters

). They can also be

linked to the Billing/TOU registers to count pulses from external
wattmeters or gas and water meters.