beautypg.com

Configuring meter security, 3 configuring meter security – SATEC EM132-133 Manual User Manual

Page 84

background image

‎Chapter 5 Configuring T H E E M 1 3 X S E R I E S

84

EM13x Series SMART MULTIFUNCTION METER

Display

Label

Parameter

Options

Default

Description

Start Day

DST Start Day

The weekday

Sunday

The 2

nd

Sunday of the

month when Daylight

Saving Time begins.

Start Hour

DST Start Hour

1-6

2

The hour when Daylight
Saving Time begins.

dSt.E

DST End

Weekday

Month-week-weekday

Week = 1, 2, 3, 4 or L

(last week of the month)

First Sunday

in November

The date when Daylight

Saving Time ends.

End Mon

DST End Month

January to December

November

The month when Daylight

Saving Time ends.

End Week

DST End Week

1

st

to 4

th

and last

First

The 1

st

week of the month

when Daylight Saving Time

ends.

End Day

DST End Day

The weekday

Sunday

The 1

st

Sunday of the

month when Daylight

Saving Time ends.

End Hour

DST End Hour

1-6

2

The hour when Daylight

Saving Time ends.

Clock Sync

Time

Synchronization

Input

None

DI1 1PPM

DI2 1PPM
DI3 1PPM

DI4 1PPM
DI5 1PPM

DI6 1PPM
DI7 1PPM


DI14 1PPM

None

The external port receiving

the time synchronization

pulses

Daylight Saving Time

When the daylight saving time is enabled, the meter automatically
advances the device clock by one hour when daylight saving time
begins and puts the clock back one hour when it ends. The default
daylight saving time change points are preset for the U.S.A.

The daylight saving time option is disabled in the PM130 by default. If
the daylight saving time option is disabled, you need to manually
adjust the device clock for daylight saving time.

Time Synchronization Pulses

External time synchronization pulses can be delivered through one of
the digital inputs.

If a digital input is selected as the time synchronization source, the
edge of an external pulse adjusts the device clock at the nearest whole
minute. The time accuracy could be affected by the debounce time of
the digital input, and by the operation delay of the external relay.

5.3 Configuring Meter Security

This setup allows changing the user password and enabling or disabling
password protection. The EM13X Series provides 3 configurable
passwords.

The password in your meter is preset to 0 at the factory, and password
protection is disabled.