‎Chapter 5 Configuring T H E E M 1 3 X S E R I E S

EM13x Series SMART MULTIFUNCTION METER

67

Figure ‎5-5: TCP Notification Client Setup Tab

The following table lists available client options.

Table 7: TCP Notification Client Setup Options

Parameter

Options

Default

Description

Client Enabled

NO, YES

NO

Enables operations of the

notification client

Server IP Address

192.168.0.3

The IP address of the notification

server

Server Port

0-65535

502

The TCP service port of the

notification server

Message Exchange

Address

0-65535

1000

The start address of a block

of 16 Modbus registers for receiving

notification messages

Connections with a remote server are triggered via programmable
setpoints. To send event notifications to a server, configure a setpoint
to respond to desired triggers or to periodic time events and put the
"Notification" action to the setpoint action list (see

Configuring

Alarm/Control Setpoints

).

See the PM130 PLUS Modbus Reference guide for more information on
operation of the notification client and the notification message
structure.

5.2 General Meter Setup
Basic Meter Setup

This section describes how to configure the EM13X Series for your
particular environment and application.

Before operating your meter, provide the device with basic information
about your electrical network.