beautypg.com

Using the front display, Using pas – SATEC EM132-133 Manual User Manual

Page 70

background image

‎Chapter 5 Configuring T H E E M 1 3 X S E R I E S

70

EM13x Series SMART MULTIFUNCTION METER

Using the Front Display

Select Options from the main menu. See

Viewing and Changing Setup

Options

in Chapter 3 for information on configuring parameters via the

front display.

Using PAS

Select General Setup from the Meter Setup menu, and then click on
the Device Options tab.

Table 10 lists available device options.

Table 10: User-configurable Device Options

Display

Label

Parameter

Options

Default

Description

TestMode

Energy Test

Mode

Three options:

OFF = disabled

Wh pulses

varh pulses

Disabled

Setting this option puts the

meter into the energy test

mode (see

Energy Pulse

LED

in Chapter 3)

PowMode

Power

Calculation

Mode

Reactive = using reactive power

S=f(P, Q),

NonActive = using non-active

power Q=f(S, P)

S=f(P, Q) The method used for

calculating reactive and

apparent powers (see

Power Calculation Modes

below)

EngyRoll

Energy Roll

Value

10000 = 10000 kWh

100000 = 100000 kWh

1000000 = 1000000 kWh

10000000 = 10000000kWh

100000000 = 100000000 kWh

1000000000 = 1000000000 kWh

10000000 The value at which energy

counters roll over to zero

Phs.Engy

Phase Energy

Calculation

Disabled

Enabled

Disabled

Enables phase energy

calculations

StrtVolt

Starting

Voltage

1.5-5.0%

1.5%

The device starting voltage

in percent of FS (120V or

400V)

Resolution

Device

Resolution

Low

High

Low

The voltage, current and

power resolution on the

front display (see

Measurement Units

in

Chapter 3) and in

communications (see
communication guides)

Options TestMode
OFF