Using the front display, Using pas – SATEC EM132-133 Manual User Manual
Page 70

Chapter 5 Configuring T H E E M 1 3 X S E R I E S
70
EM13x Series SMART MULTIFUNCTION METER
Using the Front Display
Select Options from the main menu. See
Viewing and Changing Setup
Options
in Chapter 3 for information on configuring parameters via the
front display.
Using PAS
Select General Setup from the Meter Setup menu, and then click on
the Device Options tab.
Table 10 lists available device options.
Table 10: User-configurable Device Options
Display
Label
Parameter
Options
Default
Description
TestMode
Energy Test
Mode
Three options:
OFF = disabled
Wh pulses
varh pulses
Disabled
Setting this option puts the
meter into the energy test
mode (see
Energy Pulse
LED
in Chapter 3)
PowMode
Power
Calculation
Mode
Reactive = using reactive power
S=f(P, Q),
NonActive = using non-active
power Q=f(S, P)
S=f(P, Q) The method used for
calculating reactive and
apparent powers (see
below)
EngyRoll
Energy Roll
Value
10000 = 10000 kWh
100000 = 100000 kWh
1000000 = 1000000 kWh
10000000 = 10000000kWh
100000000 = 100000000 kWh
1000000000 = 1000000000 kWh
10000000 The value at which energy
counters roll over to zero
Phs.Engy
Phase Energy
Calculation
Disabled
Enabled
Disabled
Enables phase energy
calculations
StrtVolt
Starting
Voltage
1.5-5.0%
1.5%
The device starting voltage
in percent of FS (120V or
400V)
Resolution
Device
Resolution
Low
High
Low
The voltage, current and
power resolution on the
front display (see
Measurement Units
in
Chapter 3) and in
communications (see
communication guides)
Options TestMode