IAI America PCON-CFA User Manual
Page 45
2. ACON-C/CG,
PCON-C/CG
39
2.6.5
Full Direct Value Mode (Number of Occupied Bytes: 32)
This is the operation mode with all the values (target position, speed, etc.) set up directly using values from
PLC. Set each value in the I/O area.
The robot cylinder's effective main functions that can be controlled using this mode, are as shown in the
following table.
ROBO cylinder function
{:Direct control
x:Disable
Home-return operation
{
Positioning operation
{
Speed and acceleration / deceleration
setting
{
Pitch feed (inching)
{
Pressing Operation
{
Speed change during the movement
{
Operation at different acceleration and
deceleration
{
Pause
{
Zone signal output
{
PIO pattern selection
x
(1)
PLC address configuration (* “n” shows the node address of each axis.)
Parameter
No.84
ACON/PCON side
input register
PLC side output
address (bytes)
ACON/PCON side
output register
PLC side input
address (bytes)
n, n+1
n, n+1
Target Position
n+2, n+3
Current Position
n+2, n+3
n+4, n+5
n+4, n+5
Positioning Band
n+6, n+7
Command Current
n+6, n+7
n+8, n+9
n+8, n+9
Velocity
n+10, n+11
Current Speed
n+10, n+11
n+12,
n+13
Alarm
Code n+12,
n+13
3
Zone boundary +
n+14, n+15
n+14, n+15
n+16,
n+17
n+16, n+17
Zone boundary -
n+18, n+19
n+18, n+19
Acceleration
n+20,
n+21
n+20, n+21
Deceleration
n+22,
n+23
n+22, n+23
Pressing Current Limit Value
n+24, n+25
n+24, n+25
ACON
Occupied area
PCON
Load current
threshold
n+26, n+27
n+26, n+27
Control Signal 1
n+28, n+29
Occupied area
n+28, n+29
Control Signal 2
n+30, n+31
Status Signal
n+30, n+31
(Note)
The areas denoted by Occupied area cannot be used for any other purpose.
Also, exercise caution to avoid node address duplication.