beautypg.com

IAI America PCON-CFA User Manual

Page 198

background image

4. SCON-CA

192

(3) I/O signal assignment

(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)

Signal Type

Bit

Symbol

Contents

Details

Target

Position

32-bit

data

-

32-bit signed integer indicating the current position
Set the target position on the absolute coordinates.
The unit is 0.01mm and settable range is–999999 to +999999.
(Examle) When it is “+25.41mm”, set it as “2541”.
If the value larger than the value (0.2mm) inside the soft limit
for the parameter, the movement would be limited to the inside
the soft limit (0.2mm).
* When the input is performed in hexadecimal notation, input

the negative value using a complement of 2.

4.8 (3)

Positioning

Band

32-bit

data

-

32-bit integer
The unit is 0.01mm and settable range is 1 to +999999.
(Example) When it is “25.40mm”, set it as “2540”.
This register value has two meanings depending on the
operation type.
1) In the case of positioning operation, it shows the allowable

range from the target position, that is regarded as the
positioning completion.

2) In the case of pressing operation, it shows the pressing

width value. Specify the normal operation or pressing
operation using the “PUSH” control signal setting.

4.8 (3)

Velocity

32-bit

data

-

32-bit integer
Specify the speed at which to move the actuator.
The unit is 0.01 mm/sec and the settable range is 0 to 999999.
(Example) When it is “25.41mm/sec”, set it as “2541”. When
the movement command is set with the value bigger than the
max. speed, an alarm is issued.

4.8 (3)

PLC Output

Zone

boundary+

/Zone

boundary–

32-bit

data

-

32-bit signed integer indicating the current position
After completion of home return, an effective zone signal can
be output separately from the zone boundaries specified by
parameters.
The status signal PZONE turns ON when the current position
is inside these +/- boundaries. (Example) When it is
“+25.40mm”, set it as “2540”.
The unit is 0.01mm and the settable range is -999999 to
999999.
Enter a value that satisfies the relationship of “Zone boundary
+ > Zone boundary –”.
If this function is not used, enter the same value for both the
positive and negative boundaries.
*When the input is performed in hexadecimal notation, input

the negative value using a complement of 2.

4.8 (3)

This manual is related to the following products: