Code Message

Description

301
302
304
305
306
308
30A
30B

Overrun error (M)
Framing error (M)
SCIR-QUE OV (M)
SCIS-QUE OV (M)
R-BF OV
Response timeout (M)
Packet R-QUE OV
Packet S-QUE OV

An error occurred in serial communication with the controller.
Cause:

[1] Garbage data due to noise

[2] Duplicate slave numbers when multiple actuators are

controlled via serial communication

Action:

[1] Revise the wiring, equipment layout, etc., to eliminate noise.

[2] Change the slave numbers to eliminate duplication.

If the message persists, please contact IAI.

307
309

Memory command denied
Write address error

A command was denied in serial communication with the controller.
An indeterminable write address error occurred in serial communication
with the controller.
These messages do not generate during normal operation. Should either
of them occur, record the entire error list before turning off the power. The
recorded error list will help us identify the cause of the problem.
Also contact IAI.

30C

No connected axis

The controller axis number cannot be recognized.
Cause:

[1] The controller is not operating properly.

[2] Only the communication line of the supplied cable

(SGA/SGB) is open.

[3] When RCP2 and ERC controllers are linked together via

SIO converters, not all link cables are connected although
24 V is supplied to all converters.

[4] The piano switches are set to the same number on multiple

controllers being linked.

Action:

[1] Check if the RDY LED on the controller is lit. If this LED is

not lit, the controller is faulty.

[2] If you have a spare teaching pendant, change to the spare

teaching pendant. Or, switch to the PC software mode and
see if the message will disappear.

[3] Connect all pairs of converter and controller using link

cables, and then supply the power.

[4] Do not set the piano switches to the same number on

multiple linked controllers.

If the message persists, please contact IAI.