beautypg.com

IAI America RCS-E User Manual

Page 48

background image

32


3.1.1

Push Force at Standstill


In the push & hold mode, enter a current-limiting value (%) in the position-data table under “Push.”
With the RCS, use a push force at standstill corresponding to a current-limiting value of approx. 70%.
The push force at standstill can be increased or decreased by increasing or decreasing the current-limiting value.
However, take note that the controller will not operate properly if the current-limiting value is 30% or below.
The table below lists the push force at standstill for each controller type when the current-limiting value is set to
70%.

Type

Motor (W)

Speed type

Push force

(N (kgf))

L 95

(9.7)

M 47

(4.8)

RA35 20

H 23

(2.4)

L 142

(14.5)

M 70

(7.2)

RA45 30

H 35

(3.6)

M 143

(14.6)

RB7525 60

H 71

(7.3)

L 238

(24.3)

M 118

(12.1)

60

H 59

(6.1)

M 198

(20.2)

Rod type

RB7530

100

H 99

(10.1)

L 142

(14.5)

M 70

(7.2)

Flat type

F45

30

H 35

(3.6)

Note: The accuracy of push force at standstill is not guaranteed. The values are provided for

reference purposes only.