3 timing chart, Timing chart – IAI America RCS-E User Manual
Page 53
37
3.2.7 Home
Return
With the standard specification, home return must be performed after the power has been input or an encoder
open or CPU error alarm has been reset. Selecting a position number and then initiating a start will cause the
controller to automatically perform home return before commencing the subsequent operation. Once home return
is complete, the home return completion output will turn ON (standard specification).
Home return alone cannot be performed using PIO. To move the actuator to the home position in a normal
condition, set a position number for which “0” is set in the position-data table under “Position,” and then issue a
movement command to that position.
With the absolute specification, home return is not necessary after the power has been input, as long as an
absolute reset was performed once.
3.3 Timing
Chart
Acc/dec Description
Minimum Maximum
T1
Start ON minimum duration
4 msec
T2
Start OFF minimum duration
4 msec
T3
Start ON
Command position hold time
6 msec
T4
Start ON
Position complete OFF delay
7 msec
T5
Position complete OFF
Moving ON delay
1 msec
T6
Pause OFF
Moving OFF delay
*1
T7
Pause ON
Moving ON delay
6 msec
T8
Position complete ON
Moving OFF delay
2 msec
T9
Completed position OFF
Position complete OFF delay
0.1 msec
1 msec
T10
Position complete ON
Completed position output delay
0.1 msec
1 msec
*1: The maximum value will vary depending on the acceleration/deceleration.
*2: After the position complete signal turned ON, wait for at least the sequencer’s scan time before checking the
completed position.
Start
Command position
Position complete
Completed position
Moving
*Pause
*2