IAI America RCS-E User Manual
Page 46
30
(5) Push (Push)
Select the positioning mode or push & hold mode.
The default value is “0.”
0:
Positioning mode (= Normal operation)
Other than 0: Push & hold mode [%]
In the push & hold mode, enter the current-limiting value to be applied to
the servo motor while the load is being pushed. With the RCS, set the
current-limiting value to approx. 70%. The controller will not operate
properly if this value is 30% or below.
The table on page 33 lists the push force at standstill for each controller
type when the current-limiting value is set to 70%. Be sure to reference this
table to set an appropriate value for your controller.
Note: If the push force is too small, a false detection of push & hold
condition may occur due to slide resistance, etc., so exercise
caution.
(6) Positioning band
(Pos. band)
The function of the positioning band varies depending on whether the
push & hold setting in (5) is “0” or “other than 0.”
[A] Push = 0 (Positioning mode)
In the positioning mode, enter the position-complete detection width
(distance to the target position), in [mm].
The distance to the target position indicates the range prior to the target
position, upon entry of the actuator in which range a position complete
signal will be output.
The default value is “0.1 [mm]” (Fig. A).
[B] Push = Other than 0 (Push & hold mode)
Enter the maximum push amount (distance from the target) in the push &
hold mode, in [mm] (Fig. B).
If the push direction corresponds to the negative direction along the
displayed coordinate axis, add a – (minus) sign to the entered value.
Fig. A
Fig. B
(B) Push = Other than 0
Distance to the position set in (2)
S
peed
S
peed
(A) Push = 0
Distance to the position set in (2)
Moving distance
Moving distance
(6) Positioning band
(6) Positioning band