IAI America RCS-E User Manual
Page 90
74
Code Error
Cause/action
0E7
Phase A/B/Z open
Encoder signal cannot be detected properly.
Cause:
[1] Open encoder extension cable or supplied actuator cable,
or poor connector contact
[2]
Faulty
encoder
Action:
[1] Check the connector for possibility of open circuit, and
examine the connection condition.
(Perform a continuity check by referring to 2-5, “Supplied
Cables.”)
If the cable is normal, the encoder may be faulty. Please contact
IAI.
0F8
Corrupt nonvolatile memory
Abnormal data was detected during the nonvolatile memory check at the
startup.
Cause: [1]
Faulty
nonvolatile
memory
[2] The memory was written more than 100,000 times.
(As a rough guide, the nominal life of nonvolatile memory is
around 100,000 rewrites.)
Action:
If the alarm occurs again after the power has been
reconnected, please contact IAI.
0F9
Abnormal expansion RAM
Abnormal data was detected during the expansion RAM check at the
startup.
Cause:
[1] Malfunction due to noise, etc.
[2]
Faulty
RAM
[3] Faulty circuit component around RAM
Action: Reconnect
the
power.
If the alarm occurs again, check for effect of noise.
If you have a spare controller, change to the spare controller. If
the alarm still occurs, noise is suspected.
If the cause cannot be specified, please contact IAI.
0FB
Abnormal FPGA
The FPGA (gate array) is not operating properly in the absolute controller.
Cause:
[1] Malfunction due to noise, etc.
[2]
Faulty
FPGA
[3] Faulty circuit component around FPGA
[4] The board in the controller is not installed properly.
Action: Reconnect
the
power.
If the alarm occurs again, check for effect of noise.
If you have a spare controller, change to the spare controller. If
the alarm still occurs, noise is suspected.
If the cause cannot be specified, please contact IAI.