52
























T1:

5 msec or more; time after selecting/entering a command position until the start input turns ON

(The scan time of the host controller must be considered.)

Note: When the start signal turns ON, the position complete output will turn OFF and the moving

output will turn ON.

The start signal must be turned OFF with the confirmation that the moving output has turned
ON while the start signal remains ON.


The remaining movement can be cancelled by turning ON the reset input during pause.
(The controller will detect a rise of the reset signal and cancel the remaining movement.)






















Command position


Start

Position complete

Completed position


Pause

Moving





Actuator movement

Speed

4 msec or less

Note

Command position


Start

Position complete

Completed position


Pause

Reset


Moving


Actuator movement

Speed

4 msec or more