B.2.3 adam-6018, Ch thermocouple input module – B&B Electronics ADAM-6066 - Manual User Manual
Page 244

ADAM-6000 Series User Manual
234
Remarks:
1.
User can configure the High alarm value in the ADAM.NET utility.
When AI value is higher than the High alarm, this bit will be 1.
2.
Users can configure the Low alarm value in the ADAM.NET util-
ity. When AI value is lower than the Low alarm, this bit will be 1.
B.2.3 ADAM-6018
8-ch Thermocouple Input Module
Address
0X
Channel Description
Attribute
Address 4X Chan
nel
Description
Attribute
00017
0
DO Value
R/W
00018
1
DO Value
R/W
00019
2
DO Value
R/W
00020
3
DO Value
R/W
00021
4
DO Value
R/W
00022
5
DO Value
R/W
00023
6
DO Value
R/W
00024
7
DO Value
R/W
00101 0
Reset
Historical
Max. Value
R/W 40001
0
AI
Value Read
00102 1
Reset
Historical
Max. Value
R/W
40002
1 AI
Value Read
00103 2
Reset
Historical
Max. Value
R/W
40003
2 AI
Value Read
00104 3
Reset
Historical
Max. Value
R/W
40004
3 AI
Value Read
00105 4
Reset
Historical
Max. Value
R/W
40005
4 AI
Value Read
00106 5
Reset
Historical
Max. Value
R/W
40006
5 AI
Value Read
00107 6
Reset
Historical
Max. Value
R/W
40007
6 AI
Value Read
00108 7
Reset
Historical
Max. Value
R/W
40008
7 AI
Value Read
00109 Average
Ch 0 ~ 7
Reset Historical
Max. Value
R/W
40009
Aver-
age
Ch 0
~ 7
AI Value
Read
00111 0
Reset
Historical
Min. Value
R/W
40011
0
Historical Max.
AI Value
Read
00112 1
Reset
Historical
Min. Value
R/W
40012
1
Historical Max.
AI Value
Read
00113 2
Reset
Historical
Min. Value
R/W
40013
2
Historical Max.
AI Value
Read
00114 3
Reset
Historical
Min. Value
R/W
40014
3
Historical Max.
AI Value
Read
00115 4
Reset
Historical
Min. Value
R/W
40015
4
Historical Max.
AI Value
Read
00116 5
Reset
Historical
Min. Value
R/W
40016
5
Historical Max.
AI Value
Read