Response message format for function code 08: The normal responses
return the station address, function code, start address, and requested
number of coil forced.
Example: 01 0F 00 11 00 0A
Function Code 16 (10 hex)
Preset values into a sequence of holding registers. Request message for-
mat for function code 16:
Example: Preset constant #1 (address 40009) to 100.0 in ADAM-6000
module.
01 10 00 09 00 02 04 42 C8 00 00
Response message format for function code 08: The normal responses
return the station address, function code, start address, and requested
number of registers preset.
Example: 01 10 00 09 00 02