3 analog input command set, Analog input command set – B&B Electronics ADAM-6066 - Manual User Manual
Page 140
ADAM-6000 Series User Manual
130
6.4.3 Analog Input Command Set
(ADAM-6015, 6017, 6018)
Command
Syntax
Command
Name
Description
#aan
Read Analog
Input from
Channel N
Return the input value from the specified analog input
channel
#aa
Read Analog
Input from all
channels
Return the input values from all analog input channels
$aa0
Span
Calibration
Calibrate the analog input module to correct the gain
error
$aa1
Offset
Calibration
Calibrate the analog input module to correct the offset
error
$aa6
Read Channel
Enable/Disable
Status
Asks a specified module to return the Enable/Disable
status of all analog input channels
$aa5mm
Set Channel
Enable/Disable
Status
Set Enable/Disable status for analog input channels
#aaMH
Read all
Max. Data
Read the maximum data from all analog input
channels
#aaMHn
Read single
Max. Data
Read the maximum date from a specified analog input
channel
#aaML
Read all
Min. Data
Read the minimum data from all analog input
channels
#aaMLn
Read single
Min. Data
Read the minimum data from a specified analog input
channel
#aaDnd
Set Digital
Output
Sets the status for the specified digital output channels
$aaBnn
Read Analog
Input Range
Code
Return the input range code from the specific analog
input channel