4 analog input alarm command set set, Analog input alarm command set set – B&B Electronics ADAM-6066 - Manual User Manual
Page 154
ADAM-6000 Series User Manual
144
Example command: $01B07(cr)
response: !0112
Since the ADAM-6018 is used, we can know the range code of
channel 7 is 12, meaning “Thermocouple R (500~1750° C)”.
6.4.4 Analog Input Alarm Command Set Set
(ADAM-6015, 6017, 6018)
$aaCjAhs
Name
Set Alarm Mode
Description Sets the High/Low alarm of the specified input channel in
the addressed ADAM-6000 module to either Latching or
Momentary mode.
Syntax $aaCjAhs(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave network address of an ADAM-6000 module.
(Always 01)
Cj identifies the desired channel j (j : 0 to 7).
Command
Syntax
Command
Name
Description
$aaCjAhs
Set Alarm
Mode
Set the High/Low alarm in either Momentary or Latch-
ing mode
$aaCjAh
Read Alarm
Mode
Returns the alarm mode for the specified channels
$aaCjAhEs
Enable/Dis-
able Alarm
Enables/Disables the high/low alarm of the specified
channels
$aaCjCh
Clear Latch
Alarm
Resets a latched alarm
$aaCjAhCCn Set Alarm
Connection
Connects the High/Low alarm of a specified input
channel to interlock with a specified output channel
$aaCjRhC Read Alarm
Connection
Returns the alarm configuration of a specified input
channel
$aaCjAhU
Set Alarm
Limit
Sets the High/Low alarm limit value to a specified
channel
$aaCjRhU
Read Alarm
Limit
Returns the High/Low alarm limit value of the speci-
fied channel
$aaCjS
Read Alarm
Status
Reads whether an alarm occurred in the specified
channel