ADAM-6000 Series User Manual

140

#aaMLn
Name

Read Minimum Value from channel N

Description Read the minimum value from a specific analog input

channel in a specified module

Syntax #aaMLn(cr)

# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of the ADAM-6000 module to be read.
(Always 01)
ML represents the read minimum value command.
n (range 0-8) represents the specific channel you want to
read the input data.
(cr) is the terminating character, carriage return (0Dh)

Response

>(data)(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the address does not exist.
> delimiter indicating a valid command was received.
? delimiter indicating the command was invalid.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of an ADAM-6000 module.
(cr) is the terminating character, carriage return (0Dh)

Example

command: #01ML3(cr)
response: >+10.000

The command asks the specific module at address 01h to
send historic minimum value from analog input channel 3.