#aaMLn
Name
Read Minimum Value from channel N
Description Read the minimum value from a specific analog input
channel in a specified module
Syntax #aaMLn(cr)
# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of the ADAM-6000 module to be read.
(Always 01)
ML represents the read minimum value command.
n (range 0-8) represents the specific channel you want to
read the input data.
(cr) is the terminating character, carriage return (0Dh)
Response
>(data)(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the address does not exist.
> delimiter indicating a valid command was received.
? delimiter indicating the command was invalid.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of an ADAM-6000 module.
(cr) is the terminating character, carriage return (0Dh)
Example
command: #01ML3(cr)
response: >+10.000
The command asks the specific module at address 01h to
send historic minimum value from analog input channel 3.