137
Chapter 6
#aaMH
Name
Read Maximum Value
Description Read the maximum values from all analog input channels in
a specified analog module
Syntax #aaMH(cr)
# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of the ADAM-6000 module to be read.
(Always 01)
MH represents the read maximum value command.
(cr) is the terminating character, carriage return (0Dh)
Response
>(data)(data)(data)(data)(data)(data)(data)(data)(data)(cr)
if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the address does not exist.
> delimiter indicating a valid command was received.
? delimiter indicating the command was invalid.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of an ADAM-6000 module.
(cr) is the terminating character, carriage return (0Dh)
Example
command: #01MH(cr)
Response
+10.000+10.000+10.000+10.000+10.000
+10.000 +10.000+10.000+10.000
The command asks the specific module at address 01h to
send historic maximum value from analog input channels.
Note:
The latest data returned is the Average value of the preset