beautypg.com

Sagem 3p@c – Sagem 4450E User Manual

Page 71

background image

SAGEM 3P@C

3P@C Installation Manual

Page 4-10

Reproduction and communication in any form prohibited without the written permission of SAGEM SA

1.1.1.41

1.1.1.41

1.1.1.41

1.1.1.41

Position the cabinet

A. Determine the cabinet installation position

The position of the cabinet should be determined according to the benchmark sizes specified in the floor design
of the equipment room. In determining the installation positions, avoid interference between the mounting
support and the skeleton of the antistatic floor, i.e., try to keep the integrity of the floor skeleton. If such
interference is inevitable, remove the skeleton of the floor board where the interference occurs. It is
recommended that the center of the cabinet coincide with the center of the floorboard and all sides of the cabinet
shall be symmetrical to the central symmetric line of the antistatic floor board. If multiple cabinets are to be
installed side by side, the first cabinet should be arranged in this way.

B. Marking

Place the marking template of the cabinet (placed in the packing wooden box of the cabinet) on the antistatic
floor according to the cabinet arrangement. The cabinet marking template is illustrated in Figure 4-14. Mark all
the cabinet connection holes (four per cabinet) on the floor according to the marking template diagram, the feet
position marks (four feet per cabinet) and the cabling hole positions. The semicircle gap of the template indicates
the front direction of the rack. Mark the positioning and mounting holes of the supports on the cement floor.

Note

Make sure that the direction of the template is correct.

Figure 4-14 Cabinet marking template

4-f28 (Feet position mark)

f14 Use M12 expansion bolt

Back

C. Drill holes in the anti-static floor

Remove the marking template and drill a through-hole at each connection hole position on the antistatic floor
using a percussion drill with the

Φ

20 drill bit. To drill a hole, keep the drill bit vertical with the antistatic floor and

hold tightly the drill handle and do not shake, lest the hole be slanted.