2.4. Power Distribution System
2.4.1.
2.4.1.
2.4.1.
2.4.1. Overview
The DC distribution unit of 3P@C 4450E adopts the -48 V DC power supply. It is 4U high and is fixed
to the upper part of the equipment rack rear. The -48 V DC input power is divided into 4 tributaries
whose outputs are controlled by air switches separately. Their connection relations are shown in
Figure 2-19:
Figure 2-19 Connection relations
2.4.2.
2.4.2.
2.4.2.
2.4.2. Functional Features
Input requirements
1. -48 V single input.
2. -48 V input range: -36 ~ -72 V DC.
3. -48 V total input power: 3,300 W.
Output requirements
1. The -48 V power is output to 4 channels that are led out by wiring terminals and controlled by air
switches.
2. The rated current of the air switch is 32 A.