A pcu fan has failed, Telnet to the affected sun storedge t3+ array, Run refresh -s to verify the battery state – Sun Microsystems StorEdge 6900 Series User Manual
Page 127: Replace the battery, if necessary, Telnet to affected sun storedge t3+ array, Verify the fan state with fru stat, Replace the power cooling unit, if necessary, For internal use only
Chapter 8
Troubleshooting the Sun StorEdge T3+ Array Devices
111
For Internal Use Only
t3
power.
battery
Alarm-
Red
Y
[ Info/Action ] The
state of
power.u1pcu1.BatStat
e on diag213
(ip=xxx.20.67.213) is
Fault
Possible causes are:
1. Voltage level on
power supply and
battery have
moved out of
acceptable
thresholds.
2. The internal PCU
temp has exceeded
acceptable
thresholds.
3. A PCU fan has
failed.
Information: The state
of the batteries in the
Sun StorEdge T3+
array is not optimal.
Recommended action:
1. Telnet to the
affected Sun
StorEdge T3+
array.
2. Run
refresh -s
to verify the
battery state.
3. Replace the
battery, if
necessary
t3
power.fan
Alarm-
Red
Y
[ Info/Action ] The
state of
power.u1pcu1.Fan1Sta
te on diag213
(ip=xxx.20.67.213) is
Fault
Information: The state
of a fan on the Sun
StorEdge T3+ array is
not optimal.
Recommended action:
1. Telnet to affected
Sun StorEdge T3+
array.
2. Verify the fan state
with
fru stat.
3. Replace the power
cooling unit, if
necessary.