3.5.8 SetOperatingMode Mailbox

Function Block: SETOPERMODE

Trigger Byte: SetOperate, SetStop, SetClear

Description: The following trigger values can be used to change the current
operating mode of the module:

SETOPERATINGMODE.Out.SelectOperate

= Set Operate

SETOPERATINGMODE.Out.SelectStop

= Set Stop

SETOPERATINGMODE.Out.SelectClear

= Set Clear

3.5.9 SetSlaveMode Mailbox

Function Block: SETSLMODE

Trigger Byte: SetSlaveMode

Description: The SETSLMODE function block can be used to request the
module to sync, unsync, freeze, or unfreeze. The slave address must be selected
through the SlaveAddrIn input pin. If the operation is directed to a group of
slaves, then the group number must be set through the GroupIn input pin
parameter. The actual code that will select the operation type must be configured
through the ControlIn input pin. Please check the slave's user manual for valid
control codes.

Important Note: The next mailbox is only for Anybus firmware version 3.50 and later. Earlier

released versions do not support this feature.