9.1.4 Functional Specifications

 Easy-to-use drag and drop Busview configuration interface via ProSoft

Configuration Builder software (see PSW-PCB Datasheet)

 Monitoring and modification of process data and DPV1 acyclic data with

online slave diagnostics

 Supports PROFIBUS PA slaves on the network through DP/PA coupler or

link

 Supports up to 125 slave devices with repeaters
 Supports extended diagnostic data (DPV1)
 Supports all standardized baud rates, up to 12 Mbits/s
 Auto baud detection at all valid PROFIBUS DPV1 rates
 Supports PROFIdrive 3.1 compliant parameter read and write operations
 Supports Sync and Freeze commands
 Alarm indications and confirmations handling (DPV1)
 Supports Multicast and Broadcast telegrams (DPV1)
 CRC checksum determination of slave configuration consistency to processor
 FDT/DTM PROFIBUS Master transport communication DTM software

included (Product Number PSW-CDTM-PDPM)

Hot Standby
 Hot Standby features support the SE 140 671 CPU
 Supports up to six PTQ-PDPMV1 Hot Standby modules per rack
 Diagnostic and status words are provided for Active Primary and Passive

Secondary Master health status

 PROFIBUS switchover time will be nominal 100 ms not to exceed

300 milliseconds

 Cable break detection with segmented network slave quantity information
 PROFIBUS health messages are generated from secondary Master via FDL

ping services

 No setup parameters required. Module automatically detects Hot Standby

system

Physical
 PROFIBUS DPV1 RS-485 interface with a 9-pin D shell female connector

and isolated Opto-Couplers

 Master Status LED Indicators for Operations, Network Drop Communication,

Master Token-Hold