ProSoft Technology PTQ-PDPMV1 User Manual
Page 247

PTQ-PDPMV1 ♦ Quantum Platform
Reference
PROFIBUS DP Master Network Interface Module for Quantum
User Manual
ProSoft Technology, Inc.
Page 247 of 306
August 12, 2014
9.1.4 Functional Specifications
Easy-to-use drag and drop Busview configuration interface via ProSoft
Configuration Builder software (see PSW-PCB Datasheet)
Monitoring and modification of process data and DPV1 acyclic data with
online slave diagnostics
Supports PROFIBUS PA slaves on the network through DP/PA coupler or
link
Supports up to 125 slave devices with repeaters
Supports extended diagnostic data (DPV1)
Supports all standardized baud rates, up to 12 Mbits/s
Auto baud detection at all valid PROFIBUS DPV1 rates
Supports PROFIdrive 3.1 compliant parameter read and write operations
Supports Sync and Freeze commands
Alarm indications and confirmations handling (DPV1)
Supports Multicast and Broadcast telegrams (DPV1)
CRC checksum determination of slave configuration consistency to processor
FDT/DTM PROFIBUS Master transport communication DTM software
included (Product Number PSW-CDTM-PDPM)
Hot Standby
Hot Standby features support the SE 140 671 CPU
Supports up to six PTQ-PDPMV1 Hot Standby modules per rack
Diagnostic and status words are provided for Active Primary and Passive
Secondary Master health status
PROFIBUS switchover time will be nominal 100 ms not to exceed
300 milliseconds
Cable break detection with segmented network slave quantity information
PROFIBUS health messages are generated from secondary Master via FDL
ping services
No setup parameters required. Module automatically detects Hot Standby
system
Physical
PROFIBUS DPV1 RS-485 interface with a 9-pin D shell female connector
and isolated Opto-Couplers
Master Status LED Indicators for Operations, Network Drop Communication,
Master Token-Hold