beautypg.com

ProSoft Technology PTQ-PDPMV1 User Manual

Page 114

background image

Configuring the Processor with Concept 2.6

PTQ-PDPMV1 ♦ Quantum Platform

User Manual

PROFIBUS DP Master Network Interface Module for Quantum

Page 114 of 306

ProSoft Technology, Inc.

August 12, 2014

Using the example in the illustration, note the following values:

Total Size

Start Address

Last Address

PROFIBUS Input

991

301000

301990

PROFIBUS Output

918

403000

403917


For this example, select 3000 input registers and 4000 holding registers as
shown in the following illustration.

Note: Use these values for reference only. The illustration above indicates that you can only use
2000 registers, because the start register is at 1000 and the count is 3000. If your input requires

more than 2000 registers, refer to the following paragraph.

Important: You must configure the number of registers required for your application correctly,

otherwise the backplane driver will not transfer any data between the processor and the module.

Please note that the Input Data Size and Output Data Size parameters configured in PCB will

configure only the number of registers required for PROFIBUS data. However, the module will
require more registers for status and mailbox transfer. For this reason, you must verify the total

number of registers through the Diagnostics window.

7 In Concept, open the

F

ILE

menu, and then choose

C

LOSE

P

ROJECT

.