Mailbox Messaging
PTQ-PDPMV1 ♦ Quantum Platform
User Manual
PROFIBUS DP Master Network Interface Module for Quantum
Page 162 of 306
ProSoft Technology, Inc.
August 12, 2014
Message Information
Refer to Message Information (page 180).
Slave Address
Range 1 to 125; specifies the slave to read the configuration from.
Error Code [1 … 4]
If "Return Code" equals 3080h ("Negative indication from lower layer"), status
values according to the DP-specification may be available in "Error Code 1",
Error Codes 2 through 3 are reserved. Refer to Mailbox Messaging Error Codes
(page 180).
Return Code
Refer to Mailbox Messaging Error Codes (page 180).
Fault Information
If "Invalid other" is returned in the Message Information word in the header of the
response, information about the fault can be found here. Refer to Message
Information (page 180).
0100h: Address out of range.
0A00h: Failed to execute request. Refer to Return Codes (page 181) for
additional information.
0B00h: Remote station failure. Refer to Return Codes (page 181) for additional
information.
FF00h: Module not initialized.
Identifier Bytes [1 … n]
Refer to EN50170 Vol. 2 for information on the structure of these bytes. In
addition, refer to the documentation provided with the slave device for more
information.
6.2.4 Mailbox Message: Set Slave Address
This command makes it possible to set the node address of a specified slave, if
the slave supports this feature.
Note: The message data size depends on the actual slave implementation. Range 0 to 240 bytes.
Parameter
Description
Command Initiator
Application
Command Name
SET SLAVE ADDRESS
Command Number
0600h
Fragmented
No
Extended Header Data
Fault information may be returned in the header of the response.