ProSoft Technology PTQ-PDPMV1 User Manual
Page 249

PTQ-PDPMV1 ♦ Quantum Platform
Reference
PROFIBUS DP Master Network Interface Module for Quantum
User Manual
ProSoft Technology, Inc.
Page 249 of 306
August 12, 2014
These two data blocks (Input Data and Output Data) consist of a data structure
that provides for the movement of:
Input Data image from PROFIBUS slave devices
Output Data image for writing to PROFIBUS slave devices
PTQ Module Configuration and Status (from PTQ to Quantum)
PROFIBUS Messaging Mailbox commands (from Quantum to PTQ)
PROFIBUS Messaging Mailbox responses (from PTQ to Quantum)
9.2.3 PROFIBUS DP Architecture
The network supports multiple Master systems with several slaves.
The following table shows the most important features of:
Standard
EIN 501 70
DIN 19245
Transmission Equipment (Physical)
EIA RS-485
IEC 1158-2 (through link or coupler)
Fiber Optic Cable (not available)
Transfer Procedure
Half-duplex
Bus Topology
Linear bus with active bus termination
Bus Cable Type
Shielded twisted pair conductors
Connector
9-pin D-Sub
Number of nodes on the bus
Max: 32 with no repeaters
Max: 125 with 3 repeaters in 4 segments
Effective Range
Max Bus Cable Length Per Segment
Baud Rates (for 12 Mbit/sec cable)
1.2 km
9.6 kbps
1.2 km
19.2 kbps
1.2 km
93.75 kbps
1.0 km
187.5 kbps
0.5 km
500 kbps
0.2 km
1.5 Mbps
0.1 km
3 Mbps
0.1 km
8 Mbps
0.1 km
12 Mbps