beautypg.com

ProSoft Technology PTQ-PDPMV1 User Manual

Page 168

background image

Mailbox Messaging

PTQ-PDPMV1 ♦ Quantum Platform

User Manual

PROFIBUS DP Master Network Interface Module for Quantum

Page 168 of 306

ProSoft Technology, Inc.

August 12, 2014

Data [1 … n]
Returned data.

Fault Information and Extended Fault Information
If "Invalid Other" is returned in the Message Information word in the header of the
response, information about the fault can be found here.

Fault Information

Extended Fault Information Contents

0100h

Address out of range

-

0A00h

Failed to execute request

Refer to Return Codes (page 181).

0B00h

Remote station failure

1000h

Remote station DPV1 failure

Function_Number

1100h

Length out of range (>240 bytes)

-

1200h

Slave does not support DPV1

-

1300h

Slave not active or not present in
configuration

-

FE00h

Command not possible in "Class 2-Only"
mode

-

FF00h

Module offline (not initialized or no valid
database)

-

Error Decode, Error Code 1 and Error Code 2
If "Fault Information" contains error code 1000h, more information according to
the DPV1 specification can be found here.

6.2.7 Mailbox Message: Acyclic Data Write: Class 1

This command initiates a DPV1 Class 1 acyclic write request. Refer to EN50170
(DPV1) for more information.

Parameter

Description

Command Initiator

Application

Command Name

MSAC1 WRITE

Command Number

2100h

Fragmented

No

Extended Header Data

Fault information may be returned in the header of the response.