beautypg.com

Module status indicators – ProSoft Technology PTQ-PDPMV1 User Manual

Page 228

background image

Diagnostics and Troubleshooting

PTQ-PDPMV1 ♦ Quantum Platform

User Manual

PROFIBUS DP Master Network Interface Module for Quantum

Page 228 of 306

ProSoft Technology, Inc.

August 12, 2014

8.3

Module Status Indicators

Indicator

Color

Status

Indication

DEBUG

Green ON

Configuration/Debug Port is active

OFF

Configuration/Debug Port is inactive

CFG ERR

Red

ON

Configuration Error: This LED is illuminated when the PROFIBUS and module CRC
values do not match between input/output blocks. The module expects that the
correct CRC values will be copied from the processor to the module, otherwise the
module will be placed in STOP mode (MSTR STAT LED = RED) and the CFG ERR

LED is illuminated to warn the user.
Verify that the values match the values generated with the Calculate Checksums
button in ProSoft Configuration Builder. A function block is provided for Concept to
synchronize input CRCs with Output CRCs.
This LED will also be illuminated if one of the module’s configuration files is missing.
This LED will illuminate if the module is placed in a slot other than the one for which

it was configured.
For HSBY, the LED will illuminate if the active and remote (passive) Masters'

configuration files do not match.
After downloading new configuration file to the PTQ module
For more information on interpreting this error, refer to Word Offset 59 in Slave List

Structure.

Blinking

Major error occurred. Please contact ProSoft Technical Support. This error is
typically caused by a hardware incompatibility after firmware upgrade.

OFF

Normal operation (configuration OK)

ERR1 and

ERR2

ON

The HSBY processors tried to perform a switch while a Master was in STOP mode.
This is a critical error and the module can be soft booted from within PCB

diagnostics or the module may be reseated.

Active

Green ON

The LED is on when the module is able to communicate over the backplane.

OFF

The LED is off when the module is unable to speak with the processor. The
processor is either absent or not running.

Flashing This LED flashes on the remote (passive) Master

BAT Low

Red

OFF

The battery voltage is OK and running.

ON

The battery voltage is low or the battery is not present. The battery LED will
illuminate briefly upon the first installation of the module or if the unit has not had
power for an extended period of time. This behavior is normal; however, should the

LED come on in a working installation, please contact ProSoft Technology.

E-Link

Green ON

The Ethernet port is connected to the TCP/IP network.

E-Data

Green ON

Data is being transferred through the Ethernet port.