ProSoft Technology PTQ-PDPMV1 User Manual
Page 173

PTQ-PDPMV1 ♦ Quantum Platform
Mailbox Messaging
PROFIBUS DP Master Network Interface Module for Quantum
User Manual
ProSoft Technology, Inc.
Page 173 of 306
August 12, 2014
Command and Response Layout: Set Operating Mode
Command
Response
Message ID
(ID)
(ID)
Message information
0240h
0200h
Command
0200h
0200h
Set Operation Mode
Data size
0000h
0000h
Frame count
0100h
0100h
Frame number
0100h
0100h
Offset high
0000h
0000h
Offset low
0000h
0000h
Extended word 1 Conf Req
Req Mode
Conf. Req
Act. mode.
Extended word 2
-
-
Extended word 3
-
-
Extended word 4
-
-
Extended word 5
-
-
Extended word 6
-
-
Extended word 7
-
Appl. Specific Error Code
Extended word 8
-
Fault Information
Mode
40h: STOP
80h: CLEAR
C0h: OPERATE
Conf. Req.
00h: Confirmation is not required
01h: Confirmation required. All confirmations are automatically sent by the
Master; the user is not required to send a confirmation message.
Fault Information
If "Invalid Other" is returned in the Message Information word in the header of the
response, information about the fault can be found here. Refer to Return Codes
(page 181) for more information.
0100h: Invalid operating mode
FF00h: Module not initialized