PTQ-PDPMV1 ♦ Quantum Platform

User Manual

PROFIBUS DP Master Network Interface Module for Quantum

Page 196 of 306

ProSoft Technology, Inc.

August 12, 2014

Calculated Times for Detecting a Missing Counterpart

Baud Rate

TA[ms]

TP[ms]

TFA[ms]

12 Mbps

T

TR

= 50 ms, T

SL

= 1000 Tbits

55

≤ T

TR

1

1.5 Mbps

T

TR

= 186 ms, T

SL

= 300 Tbits

205

2

500 kbps

T

TR

= 500 ms, T

SL

= 200 Tbits

550

4

93.75 kbps (PA)

T

TR

= 2374 ms, T

SL

= 100 Tbits

2611

9

45.45 kbps (PA)

T

TR

= 14000 ms, T

SL

= 640 Tbits

15400

113

9.6 kbps

T

TR

= 23200 ms, T

SL

= 100 Tbits

25520

83

Ping Sequence

This section shows the ping sequence, and how the COM-bit in register "HSBY
Remote status" is affected under different scenarios.

The figures show the active and the remote (passive) Masters connected via the
PROFIBUS network. For each Master, the DPRAM (that is, application interface)
and the software objects that are responsible for the ping sequence are shown.

Start-up

Local (active) Master operational prior to passive
As soon as the local (active) Master is ready to communicate on the PROFIBUS
network, it would start polling for ping messages from the passive one. As soon
as it receives the first ping request, the COM-bit is altered from zero to one.