beautypg.com

ProSoft Technology PTQ-PDPMV1 User Manual

Page 226

background image

Diagnostics and Troubleshooting

PTQ-PDPMV1 ♦ Quantum Platform

User Manual

PROFIBUS DP Master Network Interface Module for Quantum

Page 226 of 306

ProSoft Technology, Inc.

August 12, 2014

The following table shows some of the possible status indicators:

Processor
Status

PTQ Module
Status

PROFIBUS
Master Status

PROFIBUS Master Status LED
Description

Normal Operation RUN (ON)

ACTIVE (ON)

COM STAT (GREEN/Solid or Flash):
Master is communicating with slaves (Solid
GREEN) or at least one (Blinking).
DBASE STAT (GREEN):
PROFIBUS has been configured.
TKN HOLD (GREEN):
PTQ is holding the PROFIBUS token.
MSTR STAT (GREEN):
Master is in OPERATE mode.

PTQ module not
communicating
with processor

PTQ module
rebooted for
DEBUG only
(HSBY)

RUN (ON) or
STOP

ACTIVE (OFF)

COM STAT (OFF):
Master is not communicating with slaves.
DBASE STAT (GREEN):
PROFIBUS has been configured.
TKN HOLD (OFF):
Master does not have the token and is
inactive.
MSTR STAT (OFF):
Master is inactive.

HSBY: After the
hot swap of the
module, the PTQ
module is
correctly SET as
the remote
(passive) Master.

RUN (ON)

ACTIVE (ON)

COM STAT (GREEN/Solid or Flash):
Master is communicating with slaves (Solid
GREEN) or at least one (Blinking).
DBASE STAT (GREEN):
PROFIBUS has been configured.
TKN HOLD (GREEN):
PTQ is holding the PROFIBUS token.
MSTR STAT (RED Blinking):
Master is in remote (passive) Master mode.

PTQ PROFIBUS
Master is stopped

RUN or STOP ACTIVE

COM STAT (OFF):
Master is not communicating with
configured slaves.
DBASE STAT (GREEN):
PROFIBUS has been configured.
TKN HOLD (GREEN):
PTQ is holding the PROFIBUS token.
MSTR STAT (RED):
Master is in STOP mode.

CPU is stopped

STOP

ACTIVE

COM STAT (OFF):
Master is not communicating with
configured slaves.
DBASE STAT (GREEN):
PROFIBUS has been configured.
TKN HOLD (GREEN):
PTQ is holding the PROFIBUS token.
MSTR STAT (RED):