Name

Description

1061

%IW1061

61

Low byte: HSBY
Local Status - from
PROFIBUS
interface
High byte: HSBY
Local number of
slaves - from
PROFIBUS
interface

High Byte

Low Byte

16

8

7

0

H

S

- - O

D

D
B

C
E

S
O

P
A


Bit

Explanation

HS

This bit indicates if the Hot Standby
functionality is enabled.
0 - HSBY disabled. Module operates as
stand-alone Master or HSBY state equals
"Not connected".
1 - HSBY enabled


1062

%IW1062

62

HSBY Message
length - from UDP
HSBY Server

See explanation of bits OD, DB, CE, SO and PA in chart
for address 1060.

1063

%IW1063

63

Low byte: HSBY
Passive Status -
from UDP HSBY
Server
High byte: HSBY
Passive number of
slaves Message
length - from UDP
HSBY Server

Refer to word 60 for explanation. This is a backup word
derived from Ethernet UDP messaging

1064 to 1165 %IW1064 to

%IW1165

64 to
65

HSBY Passive
PROFIBUS CRC32
- from UDP HSBY
Server

CRC32 checksum for PROFIBUS Master configuration
downloaded from configuration utility via UDP

1066 to 1167 %IW1066 to

%IW1167

66 to
67

HSBY Passive User
Cfg CRC32 - from
UDP HSBY Server

PTQ-PDPMV1 module configuration checksum for
module configuration downloaded from configuration
utility via UDP

HSBY Input Status Data Word Details

Quantum Address
(Example)

Unity Address
(Example)

Relative Word
Offset

Description

1060

%IW1060

60

Remote HSBY Master Status data and number
of slaves seen by this Master

1061

%IW1061

61

Local HSBY Master Status data and number of
slaves seen by this Master

Word Offset 60 HSBY Local (Active) Master Status Data

HSBY Active # of Slaves (High byte)

HSBY Active Status (Low byte)

15

8

7

0