PTQ-PDPMV1 ♦ Quantum Platform

Diagnostics and Troubleshooting

PROFIBUS DP Master Network Interface Module for Quantum

User Manual

ProSoft Technology, Inc.

Page 237 of 306

August 12, 2014

Local PB Mstr:
Same as offset word 61

Low byte: HSBY local (active) Master status

High byte: HSBY active number of slaves

High Byte

Low Byte

16

8

7

0

HS

-

-

OD

DB

CE

SO

PA


Bit

Explanation

PA

Bits 0 to 6 refer to Remote Byte reference above.

SO

CE

DB

OD

-

-

HS

This bit indicates whether or not the Hot Standby functionality is enabled.
0 - HSBY disabled. Module operates as stand-alone Master or HSBY-state equals "Not

connected".
1 - HSBY enabled

HSBY UDP Message:
Same as offset word 62. This is the UDP message length.

Msg in HEX:
Same as offset word 63 to 67. UDP message containing passive low byte,
passive high byte, passive CRC32 checksum for PROFIBUS Master
configuration, and CRC32 checksum for the module configuration.

Viewing Control Registers

Press [3]

to view information about the PROFIBUS Master’s Control Registers.

Use this command to view general information about the module, such as the
firmware version and its serial number. The module status contains two possible
codes:
 0400 = module is running but not communicating with slaves
 0401 = module is running and communicating with slaves
If the module is in STOP mode, the status code will show as 0400.