Configuring the Module

PTQ-PDPMV1 ♦ Quantum Platform

User Manual

PROFIBUS DP Master Network Interface Module for Quantum

Page 36 of 306

ProSoft Technology, Inc.

August 12, 2014

To install GSD files manually

1 In ProSoft Configuration Builder tree view, click [+] to expand the PTQ-

PDPMV1 tree, and then double-click the PROFIBUS

DP icon. This action

opens the PROFIBUS Master Setup dialog box.

2 Click the C

ONFIGURE

PROFIBUS button. This action opens the ProSoft

Configuration Builder for PROFIBUS application.

3 Click

[+] to expand the PROFIBUS DP tree.

4 Click the right mouse button to open a shortcut menu.
5 On the shortcut menu, choose I

NSTALL NEW

GS*

FILE

. This action opens a

dialog box that allows you to browse for the location of the GSD configuration
files to install.

6 Choose the file to install, and then click O

PEN

. If the file already exists in the

configuration file path (see Tip above), you will be prompted to overwrite the
file.

7 You will be prompted to associate the GSD configuration file with a bitmap

image of the slave device. Use the File Open dialog box to browse for the
location of the image file to use.

Note: This procedure does not automatically copy GSD configuration files from their original
location to the GSD file path. In order to load GSD files automatically the next time you start

ProSoft Configuration Builder, copy the files to the configuration file path in the Tip above.

2.3.2 Configuring the PROFIBUS Slaves

There are two essential steps to configuring a slave:

1 Add the slave in ProSoft Configuration Builder (PCB) as a device connected

to the PROFIBUS Master, specifying the slave address and any necessary
input and output configuration. Download the PROFIBUS Master
configuration to the PTQ-PDPMV1 module.

2 Configure the slave (using PCB or the configuration tool supplied by the

manufacturer, for some PROFIBUS slaves). Verify that the slave address
configured in the slave module matches the slave address configured in PCB.
Download the PROFIBUS Slave configuration to the slave module.