Hot Standby Support

PTQ-PDPMV1 ♦ Quantum Platform

User Manual

PROFIBUS DP Master Network Interface Module for Quantum

Page 216 of 306

ProSoft Technology, Inc.

August 12, 2014

The Watchdog Time, Delta Ttr and other parameters can only be edited by
selecting the User-Defined profile.

When the "Hot Standby System" checkbox is marked, the PCB Master
configuration tool follows the rules below:

Parameter Calculation

Ttr is to be doubled in order to support one "passive" and one "active" Hot
Standby Master on the same network. Note that the Watchdog value also must
be recalculated because of the doubled Ttr.

To allow a switchover the Watchdog value that is calculated from the Ttr must be
increased. Two new parameters are introduced: HsbyWatchdogFactor and Host
Delay Time. The watchdog is calculated according to the following equation:

Watchdog = (Calculated watchdog * HsbyWatchdogFactor) + Host Delay Time

The HsbyWatchdogFactor for different baud rates is defined in the following
table:

Baud Rate

XML Keyword

Value

9.6 kBaud

HsbyWdFactor_9_6k

1

19.2 kBaud

HsbyWdFactor_19_2k

1

45.45 kBaud

HsbyWdFactor_45_45k

1

93.75 kBaud

HsbyWdFactor_93_75k

1

187.5 kBaud

HsbyWdFactor_187_5k

1

500 kBaud

HsbyWdFactor_500k

1

1.5 MBaud

HsbyWdFactor_1_5M

2

3 MBaud

HsbyWdFactor_3M

2

6 MBaud

HsbyWdFactor_6M

2

12 MBaud

HsbyWdFactor_12M

2

The Host Delay Time is set to 300 ms in the PCB Master configuration.

Invalid Master addresses:
1
The Master address must not equal 0.
2 The Master address must not equal any assigned slave address + 1.

Invalid Slave addresses:
1
A slave address must not equal the assigned Master address - 1.