Selecting the Display Language: A1-00
D
Use constant A1-00 to select the language displayed by the Inverter. A value of 0 sets English and a
value of 1 sets Japanese.
D
This user constant is not returned to the factory setting when constants are initialized. It must be manu-
ally reset to the factory setting.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
A1-00
Language selection for
Digital Operator display
0 (English),
1 (Japanese)
--
1
(Japanese)
Q
Q
Changing the Language to English
Use the following procedure to change the display language from Japanese to English.
Step
Key Sequence
Digital Operator Display
Remarks
1
MENU
MC5
2
MC5
3
DATA
ENTER
(Language)
(Japanese)
4
DATA
ENTER
A1--00 = 1
(Japanese)
Changed to constant setting level.
5
A1--00 = 0
English
6
DATA
ENTER
Entry Accepted
Writes-in the new setting.
Select Language
English
After a few seconds, the Operator dis-
play is as shown on the left.
The display language has been set to English.
J
Setting the Access Level: A1-01
D
Use constant A1-01 to select the user constant access level. This level determines which user constants
can be changed and displayed.
D
The user constants that can be displayed and changed also depend upon the control method being used.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
A1-01
Constant access level
0 4
--
2 Q
Q
Q
Access Level Settings
Setting
Function
0
Operation Only
This setting allows the operation mode and initialize mode to be changed or
displayed.
Use this setting to prevent user constant settings from being changed.
1
User Program
This setting allows only the user-selected constants (up to 32) to be changed
or displayed.
Select the desired user constants in A2-01 through A2-32.
2
Quick-start
This setting allows the user constants required to start the Inverter (about 25)
to be changed or displayed.
3
Basic
This setting allows the commonly used user constants to be changed or dis-
played.
4
Advanced
This setting allows all user constants to be changed or displayed.
4
A
EXAMPLE
"