beautypg.com

Yaskawa VS-626 MC5 User Manual

Page 218

background image

User Constants

8.2.2 Autotuning Constants: C

- 10

J

Speed Control (ASR): C5

Consta

nt

Name

Set-

Facto-

Change

during

Control Methods

nt

Num-

ber

Display

Description

Set

ting

Range

Facto

ry Set-

ting

g

during

Opera-

tion

Open Loop

Vector

Flux Vector

Page

C5-01

ASR proportional
(P) gain 1

Sets the proportional gain of the speed loop
(ASR )

0.00 to
300 00

20.00

*

B

- 32

C5 01

ASR P Gain 1

(ASR.)

300.00

*

B

- 32

C5-02

ASR integral (I)
time 1

Sets the integral time of the speed loop (ASR)
in 1-second units

0.000

to

0.500

*

B

- 32

C5 02

ASR I Time 1

in 1-second units.

to

10.000

*

B

- 32

C5-03

ASR proportional
(P) gain 2

Usually setting is not necessary.

Set to change the rotational speed gain.

For flux vector control

0.00 to
300 00

20.00

*

B

- 32

C5 03

ASR P Gain 2

For flux vector control

P

=

C5-01

I

=

C5-02

P

,

I

300.00

*

B

- 32

C5-04

ASR integral (I)
time 2

For V/f control with PG

P

=

C5-03

I

=

C5-04

0.000

to

0.500

*

B

- 32

C5 04

ASR I Time 2

I

=

C5 04

C5-07

E1-04 Motor

speed
(Hz)

0

to

10.000

*

B

- 32

C5-06

ASR primary
delay time

Sets the filter time constant; the time from the
speed loop to the torque command output, in
units of 1-second

0.000

to

0.004

A

- 33

C5 06

ASR Delay Time

units of 1-second.

Usually setting is not necessary.

to

0.500

0.004

A

- 33

C5-07

ASR switching
frequency

Sets the frequency for switching between
Proportion Gain 1, 2 and Integral Time 1, 2 in
Hz units

0.0 to

0 0

A

32

C5-07

ASR Gain SW
Freq

Hz units.

The multi-function input “ASR Gain SW”

takes priority.

0.0 to
400.0

0.0

A

- 32

C5-08

ASR integral (I)
limit

Set to a small value to prevent any radical
load change. Set to 100% of the maximum

0 to
400

400

A

----

C5 08

ASR I Limit

load change. Set to 100% of the maximum
output frequency.

400

400

A

----

*

The factory setting will change when the control method is changed. (The open loop vector control factory settings are given.)

J

Carrier Frequency: C6

Constant

Name

Setting

Factory

Change

during

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

g

during

Opera-

tion

Open Loop

Vector

Flux Vector

Page

C6-01

Carrier Frequency
Upper Limit

Set the carrier frequency upper lim-
it in kHz units

2.0 to

15.0

15.0

*1

B

B

- 24

C6 01

Carrier Freq Max

it in kHz units.

5.0

*2

*1

B

B

- 24

* 1. The setting range and the factory setting of the Inverter will differ depending on its capacity and control method. (The value

for the 200 V class 0.4 kW Inverter in open loop vector control mode is given.) (See page - 35.)

* 2. For a 400 V Inverter, if the carrier frequency is set to a value higher than the factory setting, the Inverter overload “OL2” detec-

tion value will decrease.

8