Yaskawa VS-626 MC5 User Manual

Page 106

background image

6.1

Common Settings

- 3

J

Control Method: A1-02

D

Select one of the four control methods.

D

This constant is not initialized by the initialize operation.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

A1-02

Control method selec-
tion

2 3

--

2

Open
Loop

Vector

Q

Q

D

Control Method Settings

Setting

Control Method

Function

2

Open loop vector control

Vector control using the Inverter’s internal speed information

3

Flux vector control

Vector control using a PG Speed Control Card

D

The characteristics of each control method are shown in Table 6.1.

Table

6.1

Control Method Characteristics

Characteristic

Open Loop Vector

Flux Vector

Basic control method

Current vector control without PG

Current vector control with PG

Speed detector

Not required

Required

(pulse generator)

Optional speed

detectors

Not required

PG-B2 or PG-X2

Speed control range

1:100

1:1000

Starting torque

150%/1 Hz

150%/0 r/min

Speed control

accuracy

0.2%

0.02%

Torque limit

Possible

Possible

Example applications

S Variable speed drive applications.

S Simple servo drives.
S Precision speed control.

6