7.3
Common Functions
- 61
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
o1-04
Frequency units of
constant setting
0 1
--
0
B
D
Settings
Setting
Unit
0
Unit of setting: Hz
1
Unit of setting: r/min
Constant Number Display Selection: o1-05
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
o1-05
Constant No. display
selection
0 1
--
0
A
A
D
Settings
Setting
Function
0
Display constant number
1
Display constant number (address) set for MEMOBUS communications
J
Key Function Settings/Other Settings: o2-01 to o2-08
LOCAL/REMOTE Key Enable/Disable: o2-01
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
o2-01
LOCAL/REMOTE key
enable/disable
0 1
--
1
B
B
D
This constant enables or disables the LOCAL/REMOTE Key (the Operation Mode Selector Key) on
the Digital Operator.
D
Settings
Setting
Function
0
Disabled. (Cannot change between local and remote.)
1
Enabled. (Pressing the LOCAL/REMOTE Key switches control of operation between the Oper-
ator and the sources specified in constants b1-01 and b1-02.)
STOP Key During Control Circuit Terminal Operation: o2-02
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
o2-02
STOP Key during con-
trol circuit terminal op-
eration
0 1
--
1
B
B
D
This constant enables or disables the STOP on the Digital Operator
D
Settings
Setting
Function
0
Disabled. (The STOP Key is disabled when the run command is input from an external termi-
nal.)
1
Enabled. (The STOP Key is enabled at all times during operation.)
User Constant Initial Value: o2-03
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
o2-03
User constant initial val-
ue
0 to 2
--
0
B
B
D
This constant is used to record or clear the user constant defaults.
7