Yaskawa VS-626 MC5 User Manual
Page 47
Wiring
3.4.5 Wiring the Main Circuits
- 14
Installing a Surge Absorber
Always use a surge absorber or diode for inductive loads near the Inverter. These inductive loads include
magnetic contactors, electromagnetic relays, solenoid valves, solenoids, and magnetic brakes.
Wiring the Power Terminals of Inverters with 18.5 to 75 kW Outputs
D
For 200 V class Inverters of 18.5 to 75 kW or 400 V class Inverters of 18.5 to 45 kW, connect the r
and
terminals to the R and S terminals respectively. (These are shorted by a short-circuit bar for ship-
ping.)
D
For 400 V class, 55, 75 kW, connect the r and 400 terminals to the R and S terminals respectively.
(These are shorted by a short-circuit bar for shipping.)
Installing a Noise Filter on Power Supply Side
Install a noise filter to eliminate noise transmitted between the power line and the Inverter.
D
Wiring Example 1
MCCB
Power
supply
MCCB
Noise
filter
VS-626MC
5
IM
Other
controllers
Use a special-purpose noise filter for In-
verters.
Fig
3.8
Correct Power supply Noise Filter Installation
D
Wiring Example 2
General-
purpose
noise filter
General-
purpose
noise filter
MCCB
Power
supply
MCCB
MCCB
Power
supply
MCCB
VS-626MC
5
IM
Other
controllers
VS-626MC
5
IM
Other
controllers
Do not use general-purpose noise filters. No gen-
eral-purpose noise filter can effectively suppress
noise generated from the Inverter.
Fig
3.9
Incorrect Power supply Noise Filter Installation
3