4.2Modes

- 9

Setting a User Constant in the Basic Access Level

The function level will be displayed when the DATA/ENTER Key is pressed at the programming mode
display.
Use the following display to set the acceleration time to 20.0 s.

Step

Key Sequence

Digital Operator Display

Remarks

1

MENU

MC5

Main Menu

Operation

2

Press twice.

MC5

Main Menu

Programming

3

DATA

ENTER

Function b1

Sequence

Changed to constant reading (func-
tion) level.

4

Function b2

DC Braking

5

Function C1
Accel/Decel

6

DATA

ENTER

Accel Time 1

C1

--

01 = 10

.

0 Sec

Changed to constant setting level,.

7

DATA

ENTER

Accel Time 1

0010

.

0 Sec

Selects the user constant so that the
leading 0 blinks. The blinking digit
can be changed.

8

RESET

Press twice.

Accel Time 1

0010

.

0 Sec

Blinking digit moves 2 places to the
right and the “1” blinks.

9

Accel Time 1

0020

.

0 Sec

Changes 1 to 2.

10

DATA

ENTER

Entry Accepted

Writes-in the new setting.

Accel Time 1

C1

--

01 = 20

.

0 Sec

The Operator display is as shown on
the left.

11

ESC

Function C1
Accel/Decel

Returns to “Function C1 Accel/Decel” display.

4

A

EXAMPLE

"