Appendix

12.4.6 Using an Open-collector Transistor for Operation Signals

- 14

12.4.6 Using an Open-collector Transistor for Operation Signals

CIMR-MC5A27P5 (200 V class Inverters of 7.5 kW)

3

4

5

6

7

8

11

Factory
presets

Forward Run/Stop

Forward run command
(forward run when closed)

Reverse Run/Stop

Reverse run command
(reverse run when closed)

External fault

Fault reset

Multi-step Speed
Reference 1

Multi-step Speed
Reference 2

Jog Frequency
Reference
EXTERNAL BB
command

Multi-function contact inputs

Sequence common
(Insulated from

0 V

terminal)

12

Shield terminal

1

2

12.4.7 Using Open-collector, Contact Outputs

CIMR-MC5A27P5 (200 V class Inverters of 7.5 kW)

20

19

18

10

9

27

48 V

,

50 mA

max.

26

48 V, 50 mA max.

25

Sequencer

Surge
absorber

250 VAC max

30 VDC max

Flywheel diode

48 VDC max

Flywheel diode

48 VDC max

Flywheel diode

Multi-function output
common

Open collector 2
(Default

:

Speed

agree)

Open collector

1

(Default

:

Zero

speed)

Multi-function contact output

250 V

AC,

1 A

max.

30 V

DC,

1 A

max.

(Default

:

Running signal)

Fault contact output

250 V

AC,

1 A

max.

30 V

DC,

1 A

max.

12