Yaskawa VS-626 MC5 User Manual
Page 117
Basic Operation
6.1.8 Multi-function Input Settings: H1-01 through H1-06
- 14
D
The following table shows which frequency is selected by each possible combination of multi-step
speed and JOG reference settings.
Terminal 5
Terminal 6
Terminal 7
Terminal 8
Multi-step speed
reference 1
Multi-step speed
reference 2
Multi-step speed
reference 3
JOG reference
Selected frequency
OFF
OFF
OFF
OFF
Reference 1: d1-01 (master
speed frequency)
ON
OFF
OFF
OFF
Reference 2: d1-02 (auxilia-
ry speed frequency)
OFF
ON
OFF
OFF
Reference 3: d1-03
ON
ON
OFF
OFF
Reference 4: d1-04
OFF
OFF
ON
OFF
Reference 5: d1-05
ON
OFF
ON
OFF
Reference 6: d1-06
OFF
ON
ON
OFF
Reference 7: d1-07
ON
ON
ON
OFF
Reference 8: d1-08
--
--
--
ON
Jog frequency: d1-09
Selecting 1-step and 2-step Frequency References
D
To use the master frequency (analog terminal 13 or 14), set b1-01 to 1.
D
To use frequency reference 1 (d1-01), set b1-01 to 0.
D
To use the auxiliary frequency reference (analog terminal 16), use the factory setting.
D
To use frequency reference 2 (d1-02), set H3-05 to 1F.
Frequency
reference
Reference 1
Master speed
Reference 2
Auxiliary speed
Reference 3
Reference 4
Reference 5
Reference 6
Reference 7
Reference 8
RUN/STOP
Multi-step speed reference 1
Multi-step speed reference 2
Multi-step speed reference 3
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
JOG reference
JOG frequency
Fig
6.7
Timing Chart for Multi-step Speed and JOG References
6