Wiring

3.5.1 Wire Sizes and Closed-loop Connectors

- 20

3.5

Wiring Control Circuit Terminals

A control signal line must not be longer than 50 m and must be separated from power lines.

The frequency reference must be input to the Inverter through twisted-pair wires.

3.5.1 Wire Sizes and Closed-loop Connectors

Terminal numbers and wire sizes are shown in Table 3.7.

Table

3.7

Terminal Numbers and Wire Sizes (Same for all Models)

Terminals

Terminal

Screws

Wire Thickness

[mm

2

]

Wire Type

1 to 11 13 to 33

M3.5

Stranded wire: 0.5 to
1.25
Single wire: 0.5 to 1.25

S Shielded, twisted-pair wire
S Shielded, polyethylene-covered, vinyl sheath

cable

12 (G)

M3.5

0.5 to 2

cable

The closed-loop connectors and tightening torques for various wire sizes are shown in Table 3.8.

Table

3.8

Closed-loop Connectors for Ground Terminal

Wire Thickness

[mm

2

]

Terminal

Screws

Crimp Size

Tightening Torque (N m

0.5

1.25 to 3.5

0.75

M3 5

1.25 to 3.5

0 8

1.25

M3.5

1.25 to 3.5

0.8

2

2 to 3.5

3