Setting User Constants

4.2.5 Initialize Mode

- 18

Changing Monitor Display to Output Current at Startup in Basic Access Level

Use the following procedure to change user constant o1-02 so that the output current is displayed at startup.
(The procedure continues from the end of the previous example.)

Step

Key Sequence

Digital Operator Display

Remarks

1

NJ

User Monitor Sel

Output kWatts

Check the display.

2

Power-On Monitor

Frequency Ref

3

DATA

ENTER

o1

--

02 = 1

Frequency Ref

4

Press twice.

o1--02 = 3

Output Current

5

DATA

ENTER

Entry Accepted

Writes-in the new setting.

Power-On Monitor

Output Current

After a few seconds, the Operator dis-
play is as shown on the left.

6

ESC

Function o1

Monitor Select

7

ESC

MC5

Main Menu

Programming

Output current has been set in monitor selection after power ON.

4.2.5 Initialize Mode

The initialize mode is used to select the language displayed by the Unit, the access level, and the control
method; it is also used to initialize the Unit’s user constants. The structure of the initialize mode is shown
in Figure 4.7.

Operation mode

Initialize mode

Programming mode

Language

Password

Function Selection A2

Access level

Control mode

Initialize

A2-02 User Pram 2

A2-32 User Pram 32

A2-01 User Pram 1

Accessible/settable only in Advanced setting level.

MENU

Fig

4.7

Structure of Initialize Mode User Constants

4

A

EXAMPLE

"