beautypg.com

Yaskawa VS-626 MC5 User Manual

Page 145

background image

7.1

Open-loop Vector Control

- 7

Motor No-load Current: E2-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

E2-03

(E5-03)

Motor no-load current

0.00 to
1500.0

A

1.20

Q

Q

D

The default setting depends upon the Inverter capacity.
(The table shows the default settings for 200 V class, 0.4 kW Inverters.)

D

Set the no-load current (E2-03) at the rated voltage and rated frequency. Normally this value isn’t
shown on the motor nameplate, so it might be necessary to contact the motor manufacturer.

Motor Line-to-line Resistance: E2-05

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

E2-05

(E5-05)

Motor line-to-line resist-
ance

0.000 to

65.000

9.842

A

A

D

The default setting depends upon the Inverter capacity.
(The table shows the default settings for 200 V class, 0.4 kW Inverters.)

D

Set the motor terminal resistance (U--V, V--W, and W--U) in constant E2-05. Normally this value isn’t
shown on the motor nameplate, so it might be necessary to contact the motor manufacturer for the ter-
minal resistance at the insulation class temperature. Use the following equations to calculate the resist-
ance value from the terminal resistance of a test report.

x

E-class insulation: Terminal resistance at 75

qC in the test report (:) x 0.92

x

B-class insulation: Terminal resistance at 75

qC in the test report (:) x 0.92

x

F-class insulation: Terminal resistance at 115

qC in the test report (:) x 0.87

Motor Leakage Inductance: E2-06

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

E2-06

(E5-06)

Motor leak inductance

0.0 to 30.0

%

18.2

A

A

D

The default setting depends upon the Inverter capacity.
(The table shows the default settings for 200 V class, 0.4 kW Inverters.)

D

Set the voltage drop (caused by the motor’s leakage inductance) as a percentage of the motor’s rated
voltage in constant E2-06.

D

This constant does not normally required setting because the Inverter automatically compensates dur-
ing operation.

D

Normally this value isn’t shown on the motor nameplate, so it might be necessary to contact the motor
manufacturer. It is also acceptable to set the loss (caused by the motor’s leakage inductance) as a per-
centage.

Motor Iron-core Saturation Coefficients 1, 2: E2-07, E2-08

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

E2-07

Motor iron-core satura-
tion coefficient 1

0.00 to 0.50

--

0.50

A

A

E2-08

Motor iron-core satura-
tion coefficient 2

0.00 to 0.75

--

0.75

A

A

D

Constants E2-07 and E2-08 are not required when using the motor at or below the rated frequency.

D

Set these constants when operating at a frequency higher that the motor’s rated frequency. Set the fol-
lowing values:

x

Motor iron-core saturation coefficient 1: Core-saturation coefficient when magnetic flux is 50%.

x

Motor iron-core saturation coefficient 2: Core-saturation coefficient when magnetic flux is 75%.

D

Normally these values aren’t shown on the motor nameplate, so it might be necessary to contact the
motor manufacturer. Operation will be possible with the factory-preset values.

7