Yaskawa MotionWorks IEC Hardware User Manual
Page 143

MotionWorks IEC Hardware Configuration – 2013-03-26
140
Hex Code
Description
ErrorClass
AxisErrorID
ErrorClass+AxisErrorID output from
MC_ReadAxisError
AlarmID
AlarmID output from Y_ReadAlarm
app
3407
0006
The file describing which configuration set to use was
corrupted. The default configuration set is being used.
app
3407
0007
An error occurred while writing a config file. The file
system may be full or damaged.
app
3407
0101
The configured RAM disk on the controller was unable
to be created.
app
3407
0102
Detected an unsupported option card inserted in the
controller.
app
3407
0104
Data in the controller SRAM did not match the expected
value. It should be treated as corrupted until it is re-
initialized.
app
3407
0106
The SRAM battery backup power failed. SRAM data
should be treated as corrupted until it is re-initialized.
app
3407
0107
The controller's time-of-day clock detected a voltage
decrease in the backup battery. The current time and
date is likely to be incorrect. This alarm can be cleared,
but will recur when the controller is powered ON until
the time and day is reset and the battery is replaced.
app
3407
0204
Unable to set configured network default gateway
app
3409
0001
The servo network axis node for the axis specified in
the configuration file was not found.
app
3409
0002
Axis enable failed. This problem is usually a result of
communication problems with the servo drive. It may
occur after a drive was disconnected from the
network. In this case, use Y_ResetMechatrolink to
establish communication with the drives once again.
app
3409
0003
Axis group motion activation failed. Some axes in the
group are currently under control of another group, or
motion has been blocked by the user.
app
3409
0004
The motion segment could not be added to the motion
queue because it is already queued.
app
3409
0005
Moves are prohibited when any of the group's axes are
disabled, have an alarm, or are in violation of their soft
limits.
app
340A
0001
The source for the logical input was not found, the
configured input will not be available.
app
340A
0002
The source for the logical output was not found, the