A – ArcGlide THC Serial Communication Protocol
Voltage Gain
Command ID
Data
Examples
VG
1 – 10 (1 = lowest gain)
>VG5D2< Voltage Gain set to 5.
>VG?DC< Query from the CNC.
This gain is used for closed-loop arc voltage control.
Default: 5
Use the default when using the Hypertherm lifter with the ArcGlide.
Voltage Calibration
Command ID
Data
Example
VC
900 – 1,100 (0.900 – 1.100)
>VC10005A< Sets arc voltage calibration to a
value of 1.
This value calibrates the arc voltage measurement accuracy. It is the software equivalent of adjusting the
voltage divider board to correct for small unit-to-unit tolerances. The measured arc voltage is multiplied by this
correction value before it is displayed or used for voltage control.
Default: 1.000
Language
Command ID
Data
Example
LG
0 – 6
0 = English, 1 = German,
2 = Spanish, 3 = Italian,
4 = French, 5 = Portuguese,
6 = Dutch
>LG0C3< Sets language to English.
>LG?D2< Query from the CNC.
Sets the language displayed on the ArcGlide HMI. The ArcGlide control module always displays messages in
English.
Default: 0 (English)