Site controller configurations, Site controller i, Scii and cfn3 – Gasboy CFN Site Controller User Manual
Page 69: Manual mode - gasboy 9800

Pump Interface Manual v1.3
9800/9820 Pump Dispenser
61
03/20/03
Gasboy CFN Series
Site Controller Configurations
Site Controller I
Site Controller I version 4.0 software and above will work with 9800 pumps.
Normally the Site Controller I is configured at the factory for the pump types. The pump
types are configured at TABLE 24, OFFSET 18+(PMP#-1)x4. Refer to the Site Controller I
Technical Manual to help understand the following CONFIGS.
a) 2 sided, 1 hose per pump. Byte = 64
b) 1 sided, 1 hose per pump. Byte = 74
c) 2 sided, 2 hose per pump. Byte = 65
d) 1 sided, 2 hose per pump. Byte = 75
e) 2 sided, 3 hose per pump. Byte = 66
f) 1 sided, 3 hose per pump. Byte = 76
SCII and CFN3
Configure the 9800/9820 as a Gasboy SPD. Use type 2 PCU slots. Add option 15 for singles.
Manual mode - Gasboy 9800
1.
Turn off power to the pump.
2.
Unlock and remove the front panel.
3.
Remove the two bolts located over the tabs of the bezel assembly. Lift the bezel
assembly upwards and out to remove.
4.
Loosen the two screws located on the left and right door support brackets and pivot
display panel down.
5.
Locate the switch pack SW1 on the CPU board.
6.
Close switch position 2 on SW1 for stand-alone mode (open=on line).
7.
Restore power to pump.